341
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(34)Temperature rise completion soak time setting (address: 1E3H)
Set the time for CH
Temperature rise judgment flag (RX1C to RX1F) (
Page 290, Appendix 1.1 (11)) to turn
on after the completion of temperature rise.
(a) Setting range
The setting range is 0 to 3600 (min).
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value is set to 0 (min).
(35)Sensor correction function selection (address: 1E4H)
Select the method of the sensor correction for each channel.
For details on the sensor correction function, refer to the following.
(a) Setting range
• 0H: Normal sensor correction (one-point correction)
• 1H: Sensor two-point correction
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
Default value is set to Normal sensor correction (one-point correction) (0H).
Standard
Heating-cooling
Common
b15
b0
b8
b7
b4
b3
b11
b12
CH4
CH3
CH2
CH1
to
to
to
to
Summary of Contents for NZ2GF2B-60TCRT4
Page 2: ......
Page 86: ...84 Memo ...
Page 268: ...266 Memo ...
Page 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Page 383: ...I 4 4 7 8 381 Memo ...
Page 387: ......