290
(11)CH
Temperature rise judgment flag (RX1C to RX1F)
This signal is for checking whether the temperature process value (PV) is in the temperature rise completion
range or not.
The signal turns on when the temperature process value is within the temperature rise completion range. The
signal is enabled only during module operation.
• OFF: Out of temperature rise completion range
• ON: Within temperature rise completion range
When the temperature process value (PV) stays within the temperature rise completion range during the set
temperature rise completion soak time, this signal turns to Within temperature rise completion range (ON).
Set the temperature rise completion range and temperature rise completion soak time in the following remote
buffer memory areas.
• Temperature rise completion range setting (address: 1E2H) (
• Temperature rise completion soak time setting (address: 1E3H) (
Standard
Heating-cooling
Set value
(SV)
Temperature rise
completion range
Temperature
process value (PV)
Time
Temperature rise completion soak
time setting (address: 1E3H)
CH□ Temperature rise judgment flag
(RX1C to RX1F) turns to Within
temperature rise completion range
(ON) at this point.