(32)Number of alert delay (address: 1E1H)
Set the number of sampling to judge alert occurrence.
By setting number of sampling, when the temperature process value (PV) stays within the alert area until the
number of sampling exceeds the number of alert delay, the alert status will be active.
For details on the alert function, refer to the following.
(a) Setting range
The setting range is 0 to 255 (times).
If Number of alert delay (address: 1E1H) is set to 0 (time) and the temperature process value (PV) falls within
the alert range, an alert is instantly raised (alert status).
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value is set to 0 (time).
(33)Temperature rise completion range setting (address: 1E2H)
Set the vertical range of the temperature rise completion range.
When the temperature process value (PV) meets the following conditions, the temperature rise is completed.
• (Set value (SV) - Temperature rise completion range (-))
Temperature process value (PV)
(Set value (SV)
+ Temperature rise completion range (+))
When CH
Temperature process value (PV) or CH
Process value (PV) scaling value (RWr8 to RWrB) falls
within the temperature rise judgment range, CH
Temperature rise judgment flag (RX1C to RX1F) turns on. (Set
the time taken to change the status from off to on with Temperature rise completion soak time setting (address:
1E3H).)
(a) Setting range
• When the temperature unit of the input range is
: 1 to 10 (
)
• When the temperature unit of the input range is
: 1 to 10 (
)
• Other than above: 1 to 10 (%) of the full scale
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default value is set to 1.
Standard
Heating-cooling
Standard
Heating-cooling
Temperature rise
completion range (+)
Set value (SV)
Temperature rise
completion range (-)
Temperature rise
judgment range
Setting value