287
APPENDICES
A
Appendix
1 Det
ails of
Rem
ot
e I
/O
S
ignals
Appendix
1.
1 Rem
ot
e
input
signals
(6) CH
Operation monitor (RX11 to RX14)
This signal monitors the condition of CH1 to CH4 of the temperature control module (operating or stopped). The
signal turns on during the operation and turns off when the operation is stopped.
(a) In the temperature input mode
When CH
Operation request flag (RY11 to RY14) is turned on, the signal turns on at the timing when first
conversion is completed and the temperature process value is stored in the remote register area.
(b) In the standard control mode, heating-cooling control mode, or mix control mode
When CH
Operation request flag (RY11 to RY14) is turned on, the signal turns on at the timing when the shift
to the control mode is completed.
For the timing of turning on and off CH
Operation request flag (RY11 to RY14) and the signal, refer to the
following.
• CH
Operation request flag (RY11 to RY14) (
• CH
Stop request flag (RY18 to RY1B) (
(7) Back-up of the set value completion flag (RX15)
Turning on Set value backup instruction (RY15) starts the writing of the remote buffer memory data to the non-
volatile memory. After the data writing is completed, this signal turns on. Turning off Set value backup instruction
(RY15) also turns off the signal.
For details on the data writing to the non-volatile memory, refer to the following.
Common
Common
ON
OFF
ON
OFF
Before data write
to a memory
During data write
to a memory
Completion of data
write to a memory
Status of data write to a
non-volatile memory
Controlled by the program
Set value backup
instruction (RY15)
Back-up of the set value
completion flag (RX15)
Controlled by the temperature control module