816
APPX
Appendix 4 List of Special Relay Areas
Instruction related
The following is the list of special relay areas relating to the instruction-related items.
No.
Name
Data stored
Details
Set by (setting timing) CPU
SM699
Dedicated instruction skip
flag
Off: Instruction being
executed or completed
On: Instruction not
executed
• This relay indicates whether the built-in
Ethernet function instruction (the
SP.SOCOPEN/SP.SOCCLOSE/
SP.SOCRCV/S.SOCRCVS/SP.SOCSND/
SP.ECPRTCL/SP.SLMPSND/
SP.FTPPUT/SP.FTPGET instruction),
intelligent function module dedicated
instruction, or multiple CPU dedicated
instruction has been skipped. (Checking
this flag immediately after the instruction
issue allows to determine whether or not
the dedicated instruction is non-
processing (skipped) in the internal
processing.)
• This relay saves/returns while the
interrupt program is being executed.
S (Status change)
ALL
SM700
Carry flag
Off: Carry off
On: Carry on
• This relay is a carry flag used while the
application instruction is executing.
• This relay saves/returns when the
interrupt program is being executed.
S (Instruction execution)
ALL
SM701
Number of output
characters selection
Off: Outputs until reaching
NULL code
On: Outputs 16 characters
• ASCII codes are output until reaching
NULL (00H) code, when SM701 is off.
• 16 characters of ASCII codes are output,
when SM701 is on.
• This relay saves/returns when the
interrupt program is being executed.
U
ALL
SM702
Search method
Off: Sequential search
On: Dichotomizing search
• The search method in the search
instruction can be specified by using this
relay.
• To use the dichotomizing search, data
must be sorted.
• This relay saves/returns while the
interrupt program is being executed.
U
ALL
SM703
Sort order
Off: Ascending
On: Descending
• This relay can be used to specify how to
arrange data in the sort instruction:
ascending or descending.
• This relay saves/returns while the
interrupt program is being executed.
U
ALL
SM704
Block comparison
Off: Mismatch is detected
On: Completely match
• This relay switches to on when all the
data conditions are met in the block data
comparison instruction.
• This relay saves/returns while the
interrupt program is being executed.
S (Instruction execution)
ALL
SM705
Number of conversion digits
selection
Off: Fixed number of digits
On: Desired number of
digits
• When SM705 is off, the conversion data
is specified and output with the fixed
number of digits.
• When SM705 is on, the conversion data
is specified and output with the desired
number of digits.
• This relay saves/returns while the
interrupt program is being executed.
U
Rn
SM709
DT/TM instruction improper
data detection flag
Off: No improper data
On: Improper data is
detected
• This relay switches to on when the
comparison target data is date data or
cannot be recognized as clock data, or
the comparison target device (three
words) exceeds the specified device
range in the DT/TM instruction.
• This relay saves/returns while the
interrupt program is being executed.
S (Instruction execution)/U
ALL
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......