![Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual Download Page 904](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-r00cpu/melsec-iq-r-r00cpu_user-manual_239139904.webp)
902
APPX
Appendix 9 Processing Time
I/O refresh processing time
The I/O refresh processing time for module mounted on main base unit and extension base unit can be calculated by the
following formula.
I/O refresh processing time [
s] = ((Number of input refresh points
*1
KM1) + (Number of unit having number of input points
KM2) + KM3
*3
) + ((Number of output refresh points
*2
KM4) + (Number of unit having number of output points
KM5) +
KM6
*3
)
*1 The value indicates the numeric value that is obtained through dividing the number of input points by 16.
*2 The value indicates the numeric value that is obtained through dividing the number of output points by 16.
*3 When the number of I/O points is 0, this value is handled as 0.
Condition
Constant value
MELSEC iQ-R series module
Main base unit
Input
KM1
0.04
KM2
0.56
KM3
11.2
Output
KM4
0.02
KM5
0.94
KM6
6.30
Extension base unit
Input
KM1
0.04
KM2
0.56
KM3
11.2
Output
KM4
0.02
KM5
0.94
KM6
6.30
Q series module
RQ extension base unit
Input
KM1
1.15
KM2
1.33
KM3
24.0
Output
KM4
0.03
KM5
1.20
KM6
6.21
Q series extension base unit
Input
KM1
1.85
KM2
1.98
KM3
39.4
Output
KM4
0.02
KM5
1.29
KM6
6.01
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......