![Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual Download Page 133](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-r00cpu/melsec-iq-r-r00cpu_user-manual_239139133.webp)
6 RAS FUNCTIONS
6.2 Self-Diagnostics Function
131
6
LED display setting
Set whether to display or hide the ERROR LED, USER LED, BATTERY LED, and FUNCTION LED.
[CPU Parameter]
[RAS Setting]
[LED Display Setting]
Window
Displayed items
*1 To specify whether to display or hide the FUNCTION LED, verify the versions of the CPU module and the engineering tool. (
1008 Added and Enhanced Functions)
*2 This item is not displayed on the R00CPU, R01CPU, and R02CPU. When the battery error is detected in the R00CPU, R01CPU, and
R02CPU, the ERROR LED turns on.
*3 For the R00CPU, the parameter is fixed to "None".
For the Process CPU, SIL2 Process CPU, and Safety CPU, the parameter does not appear.
For the FUNCTION LED display, the following cases have priority over the function that is set in the above setting.
• When the external input/output forced on/off function is executed (in registration) (
• When program restoration information is not written (
Page 942 Checking the program restoration information write
• When the device tests with execution conditions are registered (
Page 157 Device test with execution conditions)
Item
Description
Setting range
Default
ERROR LED
Minor Error (Continue Error)
Set whether or not to display the ERROR LED when a minor error
occurs.
• Display
• Do Not Display
Display
USER LED
Annunciator ON
Set whether the USER LED is displayed or not when annunciator (F)
ON is detected.
BATTERY
LED
Battery Error
Set whether the BATTERY LED is displayed or not when a battery
error occurs.
FUNCTION
LED
Function to use FUNCTION
LED
Set the function that uses FUNCTION LED. If FUNCTION LED is not
used, set "None".
• Data logging
function
• Memory dump
function
• None
Data logging
function
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......