320
18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION
18
SEQUENCE SCAN SYNCHRONIZATION
SAMPLING FUNCTION
Data of the CPU module are collected when each module synchronizes data with the sequence scan of the CPU module.
The modules which can synchronize and collect with sequence scan are as follows:
• MES interface module (high-speed access)
• High speed data logger module (high-speed collection)
• C intelligent function module (data sampling in sequence scan)
The following table lists the number of modules that can execute this function and the total number of points that can be
collected for a CPU module.
For details on the function using the sequence scan synchronization sampling function and collectable data for each module,
refer to the manual for the module used.
(
Manual for the module used)
Precautions
Use points in 8K-point increments to use all of the total number of points that can be collected.
The points are assigned in 8K-point increments as follows:
• 6K points used
8K points to be assigned
• 9K points used
16K points to be assigned
Item
R00CPU, R01CPU, and R02CPU
Other CPU modules
Number of executable modules
Two
Four
Total number of collectable points
16K points
32K points
RnCPU RnENCPU
RnPSFCPU RnPSFCPU RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Standard)
(Safety)
(Redundant)
(Process)
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......