APPX
Appendix 1 Error Codes
739
A
3140H
END instruction
error
• The END (FEND) instruction does
not exist in the program.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Take measures to reduce noise.
• Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At power-on,
at RESET, at
STOP
RUN
state
3141H
FB/FUN
program error
• The structure of FB/FUN program
is incorrect.
Stop
• Take measures to reduce noise.
• Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At instruction
execution
3142H
Temporary area
error
• The temporary area was used
incorrectly.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and check the program.
• Take measures to reduce noise.
• Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At instruction
execution
3143H
FB/FUN
program error
• The FB/FUN program file is
incorrect.
Stop
• Take measures to reduce noise.
• Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At instruction
execution
3160H
to
3163H
SFC program
block, step error
• The SFC program configuration is
illegal.
Stop
• Take measures to reduce noise.
• Write the SFC program to the CPU
module again. Then, reset the CPU
module and run it again. If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module. Please consult your
local Mitsubishi representative.
Error location
information
At power-on,
at RESET, at
STOP
RUN
state, at SFC
program
execution
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......