A
CFE8H
Cyclic
transmission
error (slave
station)
• There is no response from slave station.
• Check the slave station disconnection detection setting in
master station parameter (Network Configuration Settings).
• Check the existence status of slave station in network.
• Check the slave station which is disconnected.
• Take measures to reduce noise.
CFE9H
Cyclic
transmission
error (slave
station)
• The slave station of the same IP address has existed in the
same network address.
• Check the slave station where the error occurred
CFF0H
Slave station
error
• The error occurred in slave station.
• Check the slave station where the error occurred.
Error
code
Error name
Error details and cause
Action