760
APPX
Appendix 1 Error Codes
3E60H
Safety mutual
monitoring error
■
SIL2 Process CPU, SIL2 function
module
• A hardware failure has been
detected in the mutual monitoring
between the SIL2 Process CPU
and SIL2 function module.
■
Safety CPU, safety function
module
• A hardware failure has been
detected in the mutual monitoring
between the Safety CPU and
safety function module.
Stop
• Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Failure
information
At power-on,
at RESET, at
interrupt
occurrence
3E61H
Always
3E68H
Hardware failure
• A hardware failure has been
detected.
Stop
• Take measures to reduce noise.
• Check the mounting status of the CPU
module.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module.
Please consult your local Mitsubishi
representative.
Failure
information
Always
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......