636
37 FUNCTIONS
37.2 Tracking Transfer
Influence on tracking data due to safety cycle time
Safety cycle processing is performed at the interval of the specified safety cycle time, and the tracking transfer is performed
during the END processing. If the safety cycle time set in the parameter is shorter than the scan time, safety cycle processing
may be performed multiple times in a single scan. In such case, safety devices and safety labels immediately before the
tracking transfer are transferred to the other system as tracking data.
To transfer all data of safety cycle processing to the other system as tracking data, set a longer time than the scan time for the
safety cycle time. (
When data is different between the control system and the standby system
When executing the tracking transfer, files such as program (standard/safety), FB file (standard/safety), CPU parameter
(standard/safety), global label setting (standard/safety), standard/safety shared label setting must be the same between the
CPU modules of the both systems. (
Page 637 Memory Copy from Control System to Standby System)
If there is any difference, standard global devices, safety global devices, system data, and the PID control instruction
information are transferred.
*1
*1 Standard global devices and safety global devices are transferred even when the tracking transfer settings differ between the both
systems. However, devices that are included in the device range settings of the control system CPU module and not included in the
device range settings of the standby system CPU module are not reflected to the standby system CPU module. (The standby system
CPU module reflects values according to the device range settings of the standby system.)
If the files differ between the control system and the standby system, the following tracking transfer stops.
Tsc: Safety cycle time
Pg: Standard program
Scp: Safety cycle processing
Ptr: Tracking
END: END processing
(1) Tracking transfer to the standby system is performed.
Condition
Data for which the tracking transfer is stopped
When there is a difference in any of standard CPU parameter file, standard
program file, standard FB file, or standard global label setting file
• Standard local device
• Standard global label
• Standard local label
• Standard signal flow memory
When there is a difference in any of safety CPU parameter file, safety program
file, safety FB file, safety global label setting file, or standard/safety shared
label setting file
• Safety local device
• Safety global label
• Safety local label
• Standard/safety shared label
• Safety signal flow memory
Scp
Scp
Scp
Scp
Scp
Scp
Tsc
Tsc
Tsc
Tsc
Tsc
Pg
Pg
Pg
END
END
END
Pg
Pg
Pg
Pg
(1)
(1)
Ptr
Ptr
END
1 scan
1 scan
Control system
Standard control
Safety control
Interrupt
Interrupt
Interrupt
Interrupt
Interrupt
Interrupt
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......