35.8 Determination of Control System/Standby System
■
CPU parameter (redundant settings)
Set the CPU parameter in "Redundant System Settings" as follows.
Set "Global Device Setting" in "Device/Label Detailed Setting" as follows.
To switch enabling and disabling "Control System Start-up Setting (Input (X))", set a switch for the input to X30
so that "Control System Start-up Setting (Input (X))" is enabled only when the switch is on.
(1) Set "Not Set" in "Other system Start-up Timeout Setting".
(2) Set "Enable" in "Control System Start-up Setting (Input (X))".
(3) Set "X30" in "Input (X)".
(4) Set "Detailed setting" in "Tracking Device/Label Setting".
(5) Do not include X30 to X3F and Y40 to Y4F, which are used in the program example, in the tracking transfer range.
(1)
(2)
(3)
(4)
(5)