27 PROCEDURE FOR STARTING UP A REDUNDANT SYSTEM
27.2 Wiring
429
27
Wiring to the power supply modules in a redundant system
This section describes the wiring to the power supply modules.
The terminal block of each power supply module has a screw size of M4. Wire cables to the terminal block with the applicable
solderless terminal RAV1.25-4 or RAV2-4.
Separately supply power to the system A and B.
Wiring example
The following figure shows a wiring example of power cables to each main base unit and ground cables.
For wiring examples for each power supply module, refer to the manual included with the power supply module. (
Before
Using the Product)
• 100VAC, 200VAC and 24VDC wires must be twisted starting from the terminal connected, and connect
modules at the shortest distance. Also, use the thickest wire (maximum 2
) to reduce the voltage drop.
• For the wiring to a terminal block, use a solderless terminal.
• To prevent the short-circuit because of loosening screws, use the solderless terminal with an insulation
sleeve of 0.8mm or less. Note that up to two solderless terminals can be connected per terminal block.
• Ground the LG and FG terminals after short-circuiting them. Failure to do so may be susceptible to the
noise. The LG terminal has a half potential of the input voltage.
• When two redundant power supply modules operate in parallel as a redundant power supply system, it is
recommended to connect the one redundant power supply module to an AC power supply and the other
one to an uninterruptible power supply (UPS).
FG
LG
INPUT
ERR
100-240VAC
B
A
AC
AC
FG
LG
INPUT
ERR
100-240VAC
R35B
R64P
R35B
R64P
100/200VAC
100/200VAC
Terminal block
Solderless terminal
with an insulation
sleeve
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......