Appendix 1 Error Codes
3100H
Program error
• The program includes any
instruction that cannot be used or
decoded in the CPU module.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Take measures to reduce noise.
• Write the program to the CPU module
again. Then, reset the CPU module
and run it again. If the same error code
is displayed again, the possible cause
is a hardware failure of the CPU
module or module (SIL2 function
module or safety function module)
connected. Please consult your local
Mitsubishi representative.
Error location
information
At instruction
execution
3101H
Program error
• The program contains a dedicated
SFC program instruction even
although it is not an SFC program.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Take measures to reduce noise.
• Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At write, at
power-on, at
RESET, at
STOP
RUN
state
3120H
Program error
• The CPU module does not
support the dedicated instruction
executed.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Replace the CPU module with the one
that supports the instruction.
Error location
information
At power-on,
at RESET, at
STOP
RUN
state, at
instruction
execution
3121H
Program error
• The number of devices used in the
dedicated instruction specified in
the program is incorrect.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Error location
information
At instruction
execution
3122H
Program error
• The function block or function
specified in the program does not
exist.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Take measures to reduce noise.
• Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At instruction
execution
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......