APPX
Appendix 5 List of Special Register Areas
881
A
SD1890
Current safety cycle
processing time
Current safety cycle
processing time (unit:
ms)
• The current safety cycle processing time is stored. (The time is
measured in microseconds (
s).)
SD1890: The ms part is stored. (Range: 0 to 65535)
SD1891: The
s part is stored. (Range: 0 to 999)
• The measurement is stored even when the status is STOP.
S (Status
change)
RnPSF
RnSF
SD1891
Current safety cycle
processing time (unit:
s)
RnPSF
RnSF
SD1892
Minimum safety cycle
processing time
Minimum safety cycle
processing time (unit:
ms)
• The minimum safety cycle processing time is stored. (The time is
measured in microseconds (
s).)
SD1892: The ms part is stored. (Range: 0 to 65535)
SD1893: The
s part is stored. (Range: 0 to 999)
• The measurement is stored even when the status is STOP.
S (Status
change)
RnPSF
RnSF
SD1893
Minimum safety cycle
processing time (unit:
s)
RnPSF
RnSF
SD1894
Maximum safety
cycle processing time
Maximum safety
cycle processing time
(unit: ms)
• The maximum safety cycle processing time is stored. (The time
is measured in microseconds (
s).)
SD1894: The ms part is stored. (Range: 0 to 65535)
SD1895: The
s part is stored. (Range: 0 to 999)
• The measurement is stored even when the status is STOP.
S (Status
change)
RnPSF
RnSF
SD1895
Maximum safety
cycle processing time
(unit:
s)
RnPSF
RnSF
SD1903
Total standard/safety
shared label usage
capacity
Total standard/safety
shared label usage
capacity (unit: words)
The total usage capacity for labels defined in the standard/safety
shared label setting file is stored in 4-word units.
S (Status
change)
RnPSF
RnSF
SD1904
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (1st module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
SD1905
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (2nd module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
SD1906
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (3rd module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
SD1907
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (4th module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
SD1908
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (5th module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
SD1909
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (6th module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
SD1910
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (7th module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
SD1911
Start I/O number of
the CC-Link IE Field
Network safety
communication target
station (8th module)
0 to FFH: Start I/O
number
FFFFH: Not set
• The value obtained by dividing the start I/O number of the station
targeted for CC-Link IE Field Network safety communications by
16 is stored.
• When the safety communication function is not used, FFFFH is
stored.
S (Initial)
RnPSF
RnSF
No.
Name
Data stored
Details
Set by
(setting
timing)
CPU
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......