APPX
Appendix 9 Processing Time
903
A
Link refresh processing time for the network module
This section describes the link refresh processing time for the network module.
■
Link refresh processing time for the CC-Link IE Controller Network module
The link refresh processing time between the CC-Link IE Controller Network module and the modules mounted on the main
base unit and on the extension base unit can be calculated by the following formula.
T,
R [ms] = KM1 + KM2
((LB + LX + LY + SB)
16 + LW + SW) +
U
U [ms] = KM3
(SBU
16 + SWU)
•
T: Link refresh time (sending side)
•
R: Link refresh time (receiving side)
•
U: Unit label (SB/SW) refresh time
• LB: Total number of points of link relay (LB) that is refreshed by the station
*1
• LW: Total number of points of link register (LW) that is refreshed by the station
*1
• LX: Total number of points of link input (LX) that is refreshed by the station
*1
• LY: Total number of points of link output (LY) that is refreshed by the station
*1
• SB: Number of points of link special relay (SB)
*2
• SW: Number of points of link special register (SW)
*2
• SBU: Number of points of link special relay (SB)
*3
• SWU: Number of points of link special register (SW)
*3
*1 Total number of points here indicates the one of link devices that have been set in "Refresh Setting" and "Network Configuration
Settings". Note that the number of points that has been assigned in the reserved station is excluded.
*2 Number of points here indicates the one of when module label is not used. Calculation is executed while it is regarded as "0" when
module label is used.
*3 Number of points here indicates the one of when module label is used. Calculation is executed while it is regarded as "0" when module
label is not used.
*4 The base units here indicates the type of base unit where the network module targeted for refresh is mounted.
Condition
Constant value
KM1 (
10
-3
)
27
KM2 (
10
-3
)
Main base unit
0.01
Extension base unit
0.12
KM3 (
10
-3
)
Main base unit
0.03
Extension base unit
0.15
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......