![Mitsubishi Electric MELSEC iQ-R-R00CPU User Manual Download Page 747](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-r00cpu/melsec-iq-r-r00cpu_user-manual_239139747.webp)
APPX
Appendix 1 Error Codes
745
A
3302H
Pointer setting
error
• Multiple global pointers with the
same number or pointer-type
global labels are used in the
program. (The pointer numbers or
the labels are overlapping.)
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Error location
information
At power-on,
at RESET, at
STOP
RUN
state
3303H
Pointer setting
error
• Multiple local pointers with the
same number or pointer-type local
labels are used in the program.
(The pointer numbers or the labels
are overlapping.)
3320H
Interrupt pointer
setting error
• The interrupt pointer numbers
used in the files are overlapping.
3340H
FOR-NEXT
instruction error
• The NEXT instruction was not
executed even though the FOR
instruction was executed. Or,
there are more FOR instructions
than NEXT instructions.
At END
instruction
execution
3341H
FOR-NEXT
instruction error
• The NEXT instruction was
executed even though the FOR
instruction was not executed. Or,
there are more NEXT instructions
than FOR instructions.
At instruction
execution
3342H
FOR-NEXT
instruction error
• The BREAK instruction was
executed even though the FOR
instruction was not executed.
3360H
Nesting depth
error
• The number of nesting levels in
the subroutine program exceeded
its limit (16).
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the number
of nesting levels (16 or less).
Error location
information
At instruction
execution
3361H
• The number of nesting levels in
the FOR instruction exceeded its
limit (16).
3362H
• The number of nesting levels in
the DI instruction exceeded its
limit (16).
3363H
Nesting depth
error
• The number of nesting levels in
the function block or function
exceeded its limit (32).
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the number
of nesting levels (32 or less).
Error location
information
At instruction
execution
3380H
Pointer
execution error
• The pointer specified in the
instruction does not exist.
Stop
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Error location
information
At instruction
execution
3381H
• The RET instruction does not exist
in the executed subroutine
program.
At END
instruction
execution
3382H
• The RET instruction exists before
the FEND instruction in the main
program.
At instruction
execution
33A0H
Interrupt pointer
execution error
• The interrupt pointer
corresponding to the interrupt
input does not exist.
Stop
• Check if the program corresponding to
the interrupt pointer number set in the
module parameters exists.
At instruction
execution
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......