Appendix 1 Error Codes
1A60H
to
1A66H
Timeout in
safety
communications
• A timeout error occurred during
safety communications.
Continue
■
SIL2 Process CPU
• Check and correct the safety refresh
monitoring time and the transmission
interval monitoring time setting values.
• The possible cause is malfunction due
to noise or cable failure. Check that
there is no error in a transmission path
by executing CC-Link IE Field
diagnostics. Check the distance of
wires and cables and the grounding
status of each device as well.
• Check the detailed information (safety
station system configuration
information) of the error by executing
module diagnostics using the
engineering tool and check "Station
No.", "Slot No. (another station)", and
"Base No. (another station)". If the
destination station is an intelligent
device station, execute the system
monitor for the remote head module in
the station and check the error details.
• Check that no online operation is being
performed from a peripheral such as
the engineering tool, or no program or
parameter is being written to the safety
communication destination station.
• The possible cause is a hardware
failure of the module performing safety
communications. Please consult your
local Mitsubishi representative.
■
Safety CPU
• Check and correct the safety refresh
monitoring time and the transmission
interval monitoring time setting values.
• The possible cause is malfunction due
to noise or cable failure. Check that
there is no error in a transmission path
by executing CC-Link IE Field
diagnostics. Check the distance of
wires and cables and the grounding
status of each device as well.
• Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool and check the
displayed station number. If the
destination station is a remote device
station or remote I/O station, read error
history data of the destination station
by executing a command from the CC
IE Field Configuration window and
check the details of the error. If the
destination station is a master/local
station, execute the system monitor for
the station and check the details of the
error.
• Check that no online operation is being
performed from a peripheral such as
the engineering tool, or no program or
parameter is being written to the safety
communication destination station.
• The possible cause is a hardware
failure of the module performing safety
communications. Please consult your
local Mitsubishi representative.
System
configuration
information,
safety station
system
configuration
information
At interrupt
occurrence
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......