28 FUNCTIONS
28.5 System Consistency Check
477
28
File
Whether both systems have the same files is checked.
The following table shows whether or not to perform the check on each file type.
: Checked,
: Not checked,
: Storage not possible
*1 The reserved area for online change and program restoration information write status are also checked. (
a program file, Page 942 Program Restoration Information Write Selection)
*2 Whether a file is stored or not is checked. The file contents are not checked.
*3 The file will not be checked at the timing on when SD memory cards are inserted during operation.
Operation of when a mismatch is detected
If a mismatch between the files is detected, a stop error occurs on the standby system CPU module.
Set the CPU modules of both systems to have the same files with either of the following methods.
• Writing files to both systems
• Executing the memory copy from the control system to the standby system for storing the same files in both systems (
Page 468 Memory Copy from Control System to Standby System)
File type
Check target memory
Built-in memory of CPU
module
SD memory card
Program
FB file
CPU parameter
System parameter
Module parameter
Module extension parameter
Module-specific backup parameter
Memory card parameter
Device comment
Initial device value
Global label setting file
Initial label value file
Initial global label value file
Initial local label value file
File register
Event history
Device data storage file
General-purpose data
Data logging setting file
Common setting file
Individual setting file
Remote password
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......