11 DATA LOGGING FUNCTION
11.2 Data Collection Conditions
173
11
11.2
Data Collection Conditions
This section describes the timing when data is collected and the conditions under which data is collected.
Each scan
Data are collected during the END processing of each scan.
Time specification
Specify the collection time interval. Specify the timing of data collection using advanced settings as well.
Data collection at specified time interval
Data are collected at specified time interval.
Ex.
10 milliseconds (10ms)
Data collection conditions
Description
Each scan
Collects data during the END processing of each scan.
Time
specification
Data collection at specified time interval
Collects data at specified time interval.
Data collection during the END processing after
specified time interval
Collects data during the END processing after specified time interval.
Interrupt occurrence
Collects data at specified time interval after the execution of an interrupt
program.
Condition
specification
Device/label specification
Collects data when the monitored data meets the specified condition during the
END processing.
Step No. specification
Collects data when the specified condition is met immediately before the
execution of the specified step.
0
END
0
END
0
END
0
END
0
END
Program
Scan time
Scan time
Scan time
Scan time
Scan time
END processing
END processing
END processing
END processing
END processing
Sampling
Sampling
Sampling
Sampling
Sampling
10ms
10ms
10ms
Set time
Sampling
Sampling
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......