37
Effect on the scan time
The following describes the effect on the scan time depending on the tracking mode.
For the calculation method for an increase in the scan time due to tracking transfer, refer to the following.
Page 926 Increase in the scan time due to tracking transfer
■
Synchronous tracking mode
In the synchronous tracking mode, tracking transfer is always performed once every scan during the END processing. Until
the standby system receives the tracking data sent from the control system, the next scan is not started. Thus, the scan time
of the control system and standby system increases by the time for tracking data send/receive processing.
Ex.
CTRL: Program executed in the control system, MAIN: Program executed in both systems
*1 If the constant scan is used, waiting time for the constant scan generated.
In the control system, the scan time is extended by the following tracking send processing time.
In the standby system, the scan time increases by the following tracking receive processing time.
Item
Description
(1) Tracking send
processing
(2) Waiting for completion of tracking
data reflection
After receiving a notification of the reflection completion from the standby system, the
control system sends the tracking data.
(3) Sending tracking data
The control system sends the tracking data.
(4) Waiting for completion of tracking
data reception
The control system waits for a notification of receive completion from the standby
system. After receiving the notification of the receive completion from the standby
system, the control system starts another END processing.
Item
Description
(5) Tracking receive
processing
(6) Waiting for tracking data reception
The standby system receives the tracking data from the control system. After receiving
the tracking data, the standby system notifies the control system of the receive
completion and reflects the tracking data.
(7) Reflecting tracking data
The standby system reflects the tracking data. After the reflection completion, the
standby system notifies the control system of the reflection completion and starts
another END processing.
MAIN, CTRL
MAIN, CTRL
MAIN
MAIN
(6)
(2)
(3)
(1)
(6)
(4)
(5)
(7)
END
END
END
END
*1
(7)
END
END
*1
Data
received
Data
received
Data
reflected
Data
reflected
Data
reflected
Data
reflected
Scan time of the control system CPU module
Scan time of the control system CPU module
Control system
CPU module
Control system
CPU module
I/O
refresh
I/O
refresh
Standby system
CPU module
Standby system
CPU module
I/O
refresh
(input only)
I/O
refresh
(input only)
Tracking data
Tracking data
Scan time of the standby system CPU module
Scan time of the standby system CPU module
I/O
refresh
I/O
refresh
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......