274
15 CPU MODULE DATA BACKUP/RESTORATION FUNCTION
15.1 Backup Function
Operating procedure (when date and time are specified)
Data is automatically backed up on the specified date and time.
1.
Set the upper limit value for the number of CPU module backup data. (The setting method and operating procedure for
the upper limit value are the same as those for the upper limit value for the backup processing triggered by turning on
SM1351. (
Page 272 Operating procedure))
2.
Set the date and time with SD947 to SD949.
3.
To retry the automatic backup, turn on the bit 10 of SD944 (Backup function setting). For the retry of the automatic
backup, refer to the following.
Page 273 Retrying the automatic backup
4.
Turn on the bit 0 of SD944.
If the backup processing is completed with an error and SM953 (CPU module data backup error check flag) turns on, check
SD953 (Backup error cause), take actions, and then back up the data again as required.
• In months that does not have the specified date, the automatic backup is not executed. For example, when
SD947 has been set to "31", the months when the automatic backup is executed are January, March, May,
July, August, October, and December.
• If the time less than 1 hour from the start time of daylight saving time has been set with the daylight saving
time function, the automatic backup is not executed.
Operating procedure (when time and day of the week are specified)
Data is automatically backed up on the specified time on the specified day of the week.
1.
Set the upper limit value for the number of CPU module backup data. (The setting method and operating procedure for
the upper limit value are the same as those for the upper limit value for the backup processing triggered by turning on
SM1351. (
Page 272 Operating procedure))
2.
Set the time and day of the week with SD950 to SD952.
3.
To retry the automatic backup, turn on the bit 10 of SD944 (Backup function setting). For the retry of the automatic
backup, refer to the following.
Page 273 Retrying the automatic backup
4.
Turn on the bit 1 of SD944.
If the backup processing is completed with an error and SM953 turns on, check SD953, take actions, and then back up the
data again as required.
If the time less than 1 hour from the start time of daylight saving time has been set with the daylight saving
time function, the automatic backup is not executed.
Special register
Description
SD947
Set the date when the data is to be automatically backed up.
SD948
Set the time (hour) when the data is to be automatically backed up.
SD949
Set the time (minute) when the data is to be automatically backed up.
Special register
Description
SD950
Set the time (hour) when the data is to be automatically backed up.
SD951
Set the time (minute) when the data is to be automatically backed up.
SD952
Set the day of the week when the data is to be automatically backed up.
b0: Sunday, b1: Monday, b2: Tuesday, b3: Wednesday, b4: Thursday, b5: Friday, b6: Saturday
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......