12 DEBUG FUNCTION
12.1 Memory Dump Function
223
12
Error code specification
With a specified error code of the CPU module as a trigger, data is to be collected. The occurrence timing of trigger varies
depending on the error type: continuation error or stop error.
■
At the occurrence of a continuation error
The occurrence timing of trigger is at the time of END processing of the scan where an error has occurred.
In the following situations, the occurrence of a continuation error that is specified as a trigger condition is not recognized as a
trigger, with no data collection:
• After the occurrence of a continuation error that is specified as a trigger condition, the same error, or a continuation error,
has occurred again.
• In the situation that a continuation error of 15 or more has occurred, a continuation error that is specified as a trigger
condition has occurred.
Being recognized as a trigger requires the error to be cleared.
■
At the occurrence of a stop error
The occurrence timing of trigger is at the time of occurrence of an error.
To specify an annunciator number as a trigger condition, employ device specification to specify any desired
annunciator number.
RUN
END
END
RUN/STOP state
A continuation error occurs.
Trigger occurrence
Error
1 scan
Program
Data sampling starts.
RUN
STOP
RUN/STOP state
A stop error occurs.
Trigger occurrence
Error
Program
Data sampling starts.
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......