11 DATA LOGGING FUNCTION
11.7 Missing Data
193
11
11.7
Missing Data
The term "missing data" means that some of the collected data is missing, resulting in data discontinuity.
Conditions under which missing data occurs
Missing data occurs under the following conditions:
*1 Failure to collect data at the specified collection interval/timing due to the execution of a long-running instruction (such as FMOV) does
not cause processing overflow or missing data.
*2 The following operation also is included:
Online operation which displays data by operation such as read from the programmable controller performed from an engineering tool
(retrieval and display of a list of files on the CPU module)
View of the event history (retrieval of the event history from the CPU module)
Processing overflow
In normal cases when the usage of the internal buffer reaches the specified maximum capacity, the CPU module overwrites
the data stored in the storage memory on a first-in first-out basis. If the internal buffer becomes full before all of the data stored
in it is saved to the storage memory, however, the CPU module does not overwrite the existing data and stops storing data in
the internal buffer, thus resulting in missing data. This situation is referred to as processing overflow. Upon the occurrence
overflow, the special register (Number of processing overflow occurrences) stores the number of times when processing
overflow occurred.
Item
Description
Processing overflow
Processing overflow has occurred due to failure to keep up with the specified collection interval/timing.
Operations for the CPU module
The CPU module has been stopped and run with "Operation at transition to RUN" set to "Auto Start".
The CPU module has been turned off and on with "Operation at transition to RUN" set to "Auto Start".
The CPU module has been reset and run with "Operation at transition to RUN" set to "Auto Start".
Operation from engineering tools, CPU Module
Logging Configuration Tool, and external devices via
protocols such as FTP, SLMP, and MC
• When the CPU module is suspended and restarted, and operation for displaying the logging state is
performed from CPU Module Logging Configuration Tool
• File read
, write, delete, or verification
Summary of Contents for MELSEC iQ-R-R00CPU
Page 2: ......
Page 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Page 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Page 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Page 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Page 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Page 1027: ......