5 - 2
5. UL, cUL STANDARDS AND EMC DIRECTIVE
5.2 EMC Directive
5.2.1
Requirements to Meet EMC Directive
EMC Directives are those which require "any strong electromagnetic force is not output to the external.:Emission
(electromagnetic interference)" and "It is not influenced by the electromagnetic wave from the external.: Immunity
(electromagnetic sensitivity)".
Items
EMC directive thru
Grounding summarize the precautions to use GOT and configure the mechanical unit in
order to match the EMC directives.
Though the data described herein are produced with our best on the basis of the requirement items and standards of the
restrictions gathered by Mitsubishi, they do not completely guaranteed that all mechanical unit manufactured according
to the data do not always match the above directives. The manufacturer itself which manufactures the mechanical unit
must finally judge the method and others to match the EMC directives.
EMC directive
The standards of the EMC Directive are shown below.
*1
The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel.
The above test items are conducted in the condition where the GOT is installed on the conductive control panel and combined
with the Mitsubishi PLC.
*2
QP: Quasi-peak value, Mean : Average value
*3
The above test items are conducted in the following conditions.
30M-230MHz QP : 40dB V/m (10m in measurement range)
230M-1000MHz QP : 47dB V/m (10m in measurement range)
Applied standard
Test standard
Test details
Standard value
EN61131-2
: 2007
EN55011
Radiated noise
*1
Electromagnetic emissions from the
product are measured.
30M-230MHz QP:
30dB V/m (30m in measurement range)
*2, *3
230M-1000MHz QP:
37dB V/m(30m in measurement range)
*2, *3
EN61000-4-2
Electrostatic immunity
*1
Immunity test in which static electricity is
applied to the cabinet of the equipment.
4kV Contact discharge
8kV Aerial discharge
EN61000-4-3
Radiated field AM
modulation
*1
Immunity test in which field is irradiated
to the product.
80-1000MHz:10V/m
1.4-2GHz:3V/m
2.0-2.7GHz:1V/m
80%AM modulation@1kHz
EN61000-4-4
Fast transient burst noise
*1
Immunity test in which burst noise is
applied to the power line and signal
lines.
Power line:2kV
Digital I/O(24V or higher): 1kV
(Digital I/O(24V or less))> 250V
(Analog I/O, signal lines)> 250V
EN61000-4-5
Surge immunity
*1
Immunity test in which lightening surge
is applied to the product.
Power line (between line and ground): 0.5kV
Power line (between lines): 0.5kV
Data communication port: 1kV
EN61000-4-6
Conducted RF immunity
*1
Immunity test in which a noise inducted
on the power and signal lines is applied.
Power line: 10V
Data communication port: 10V
EN61000-4-8
Power supply frequency
magnetic field immunity
Test for checking normal operations
under the circumstance exposed to the
ferromagnetic field noise of the power
supply frequency (50/60Hz).
30 A/m
Summary of Contents for GT16
Page 1: ......
Page 2: ......
Page 46: ...1 4 1 OVERVIEW 1 1 Features ...
Page 54: ...2 8 2 SYSTEM CONFIGURATION 2 2 System Equipment ...
Page 60: ...3 6 3 SPECIFICATIONS 3 4 Battery specifications ...
Page 72: ...5 8 5 UL cUL STANDARDS AND EMC DIRECTIVE 5 2 EMC Directive ...
Page 102: ...6 30 6 OPTION 6 7 Connector Conversion Box ...
Page 106: ...7 4 7 INSTALLATION 7 1 Installing Procedure ...
Page 110: ...8 4 8 COMMUNICATION CABLE 8 1 Overview of Communication Cable ...
Page 130: ...9 20 9 HANDLING OF POWER WIRING AND SWITCH 9 4 Switch Wiring ...
Page 142: ...10 12 10 UTILITY FUNCTION 10 3 Utility Display ...
Page 184: ...11 42 11 DISPLAY AND OPERATION SETTINGS GOT SET UP 11 4 Maintenance Function ...
Page 202: ...12 18 12 COMMUNICATION INTERFACE SETTING COMMUNICATION SETTING 12 3 Ethernet Setting ...
Page 226: ...13 24 13 DEBUG 13 3 Memory Data Control ...
Page 248: ...14 22 14 SELF CHECK 14 2 Batch Self Check ...
Page 350: ...15 102 15 DATA CONTROL 15 3 OS Project Information ...
Page 410: ...19 22 19 TROUBLESHOOTING 19 2 Error Message and System Alarm ...
Page 418: ...App 8 APPENDICES Appendix 3 Transportation Precautions ...
Page 422: ...REVISIONS 4 ...
Page 425: ......
Page 426: ......
Page 427: ......
Page 428: ......
Page 470: ......
Page 510: ...21 22 21 COMPUTER LINK CONNECTION 21 6 Precautions ...
Page 568: ...22 58 22 ETHERNET CONNECTION 22 5 Precautions ...
Page 584: ......
Page 626: ...25 14 25 SERVO AMPLIFIER CONNECTION 25 7 Precautions ...
Page 632: ...26 6 26 ROBOT CONTROLLER CONNECTION 26 6 Precautions ...
Page 647: ...MULTIPLE GOT CONNECTIONS 29 GOT MULTI DROP CONNECTION 29 1 ...
Page 648: ......
Page 659: ...MULTI CHANNEL FUNCTION 30 MULTI CHANNEL FUNCTION 30 1 ...
Page 660: ......
Page 675: ...FA TRANSPARENT FUNCTION 31 FA TRANSPARENT FUNCTION 31 1 ...
Page 676: ......
Page 742: ...31 66 31 FA TRANSPARENT FUNCTION 31 7 Precautions ...
Page 744: ......
Page 766: ...32 22 32 CONNECTION TO IAI ROBOT CONTROLLER 32 7 Precautions ...
Page 802: ...34 10 34 CONNECTION TO OMRON TEMPERATURE CONTROLLER 34 7 Precautions ...
Page 834: ...36 18 36 CONNECTION TO KOYO EI PLC 36 6 Device Range that Can Be Set ...
Page 858: ...38 12 38 CONNECTION TO SHARP PLC 38 6 Device Range that Can Be Set ...
Page 868: ...39 10 39 CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER 39 7 Precautions ...
Page 902: ...42 6 42 CONNECTION TO TOSHIBA MACHINE PLC 42 6 Device Range that Can Be Set ...
Page 908: ...43 6 43 CONNECTION TO PANASONIC SERVO AMPLIFIER 43 7 Precautions ...
Page 970: ...48 12 48 CONNECTION TO FUJI TEMPERATURE CONTROLLER 48 7 Precautions ...
Page 1052: ...52 26 52 CONNECTION TO AZBIL CONTROL EQUIPMENT 52 7 Precautions ...
Page 1102: ...55 14 55 CONNECTION TO GE PLC 55 7 Precautions ...
Page 1114: ...57 4 57 CONNECTION TO SICK SAFETY CONTROLLER 57 5 Device Range that Can Be Set ...
Page 1128: ...59 2 59 CONNECTION TO HIRATA CORPORATION HNC CONTROLLER ...
Page 1130: ...60 2 60 CONNECTION TO MURATEC CONTROLLER ...
Page 1132: ......
Page 1270: ...62 68 62 MICROCOMPUTER CONNECTION ETHERNET 62 8 Precautions ...
Page 1271: ...MODBUS CONNECTIONS 63 MODBUS R RTU CONNECTION 63 1 64 MODBUS R TCP CONNECTION 64 1 ...
Page 1272: ......
Page 1292: ...64 12 64 MODBUS R TCP CONNECTION 64 7 Precautions ...
Page 1293: ...CONNECTIONS TO PERIPHERAL EQUIPMENT 65 VNC R SERVER CONNECTION 65 1 ...
Page 1294: ......
Page 1298: ...65 4 65 VNC R SERVER CONNECTION 65 4 Setting in Personal Computer ...
Page 1302: ...REVISIONS 4 ...
Page 1305: ......
Page 1306: ......