24 - 16
24. INVERTER CONNECTION
24.5 FREQROL Series Inverter Side Settings
24.5 FREQROL Series Inverter Side Settings
For details of the inverter, refer to the manual of each
series.
24.5.1 Connecting FREQROL-S500,
S500E, F500J series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit). Set Pr.30 (Extended function selection) to 1 [With
display] before making the parameter settings.
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual
of FREQROL-S500, S500E, and F500J series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
When being monitored from the GOT, the parameter n1
through n7 correspond with Pr.331 through Pr.337, and the
parameter n10 through n12 correspond with Pr.340 through
Pr.342.
Numbers in brackets show the parameter number when the
parameter unit is in use.
*5
There is no Protocol selection setting on the inverter side.
24.5.2 Connecting FREQROL-E500
series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit).
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual
of FREQROL-E500 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
There is no Protocol selection setting on the inverter side.
*5
The setting is required for Frequency setting command
selection.
GOT connection destination
Parameters corresponding to inverter
RS-485 port
Pr.79, n1 to n7, n10 to n12
Setting item
*1
Parameter No.
*4
Set
value
Contents of setting
Communication station
number
n1 (331)
0 to 31
24.5.13 Station
number setting
Communication speed
*2
n2 (332)
192
*3
19200bps
Stop bit length
*2
n3 (333)
10
Data length: 7bit
Stop bit length: 1bit
Parity check presence/
absence
*2
n4 (334)
1
Odd
Number of communication
retries
n5 (335)
---
(65535)
The inverter will not
come to an alarm
stop.
Communication check time
interval
n6 (336)
---
Communication check
suspension
Wait time setting
n7 (337)
0
0ms
CRLF selection
n11 (341)
1
*3
With CR
Without LF
Protocol selection
*5
-
-
-
Operation mode selection
Pr.79
0
*3
External operation
mode at power on
Link start mode selection
n10 (340)
1
Computer link
operation
E
2
PROM write selection
n12 (342)
0
*3
Written to RAM and
EEPROM
GOT connection
destination
Parameters corresponding to inverter
PU connector
Pr.79, Pr.117 to Pr.124, Pr.146, Pr.342
Setting item
*1
Parameter No.
Set
value
Contents of setting
Communication station
number
Pr.117
0 to 31
24.5.13 Station
number setting
Communication speed
*2
Pr.118
192
*3
19200bps
Stop bit length
*2
Pr.119
10
Data length: 7bit
Stop bit length: 1bit
Parity check presence/
absence
*2
Pr.120
1
Odd
Number of communication
retries
Pr.121
9999
(65535)
The inverter will not
come to an alarm
stop.
Communication check time
interval
Pr.122
9999
Communication
check suspension
Wait time setting
Pr.123
0
0ms
CRLF presence/ absence
selection
Pr.124
1
*3
With CR
Without LF
Protocol selection
*4
-
-
-
Operation mode selection
Pr.79
1
*3
PU operation mode
Communication startup
mode selection
*4
-
-
-
E
2
PROM write selection
Pr.342
0
*3
Written to RAM and
EEPROM
Frequency setting command
selection
*5
Pr.146
9999
Built-in frequency
setting
potentiometer
invalid
Summary of Contents for GT16
Page 1: ......
Page 2: ......
Page 46: ...1 4 1 OVERVIEW 1 1 Features ...
Page 54: ...2 8 2 SYSTEM CONFIGURATION 2 2 System Equipment ...
Page 60: ...3 6 3 SPECIFICATIONS 3 4 Battery specifications ...
Page 72: ...5 8 5 UL cUL STANDARDS AND EMC DIRECTIVE 5 2 EMC Directive ...
Page 102: ...6 30 6 OPTION 6 7 Connector Conversion Box ...
Page 106: ...7 4 7 INSTALLATION 7 1 Installing Procedure ...
Page 110: ...8 4 8 COMMUNICATION CABLE 8 1 Overview of Communication Cable ...
Page 130: ...9 20 9 HANDLING OF POWER WIRING AND SWITCH 9 4 Switch Wiring ...
Page 142: ...10 12 10 UTILITY FUNCTION 10 3 Utility Display ...
Page 184: ...11 42 11 DISPLAY AND OPERATION SETTINGS GOT SET UP 11 4 Maintenance Function ...
Page 202: ...12 18 12 COMMUNICATION INTERFACE SETTING COMMUNICATION SETTING 12 3 Ethernet Setting ...
Page 226: ...13 24 13 DEBUG 13 3 Memory Data Control ...
Page 248: ...14 22 14 SELF CHECK 14 2 Batch Self Check ...
Page 350: ...15 102 15 DATA CONTROL 15 3 OS Project Information ...
Page 410: ...19 22 19 TROUBLESHOOTING 19 2 Error Message and System Alarm ...
Page 418: ...App 8 APPENDICES Appendix 3 Transportation Precautions ...
Page 422: ...REVISIONS 4 ...
Page 425: ......
Page 426: ......
Page 427: ......
Page 428: ......
Page 470: ......
Page 510: ...21 22 21 COMPUTER LINK CONNECTION 21 6 Precautions ...
Page 568: ...22 58 22 ETHERNET CONNECTION 22 5 Precautions ...
Page 584: ......
Page 626: ...25 14 25 SERVO AMPLIFIER CONNECTION 25 7 Precautions ...
Page 632: ...26 6 26 ROBOT CONTROLLER CONNECTION 26 6 Precautions ...
Page 647: ...MULTIPLE GOT CONNECTIONS 29 GOT MULTI DROP CONNECTION 29 1 ...
Page 648: ......
Page 659: ...MULTI CHANNEL FUNCTION 30 MULTI CHANNEL FUNCTION 30 1 ...
Page 660: ......
Page 675: ...FA TRANSPARENT FUNCTION 31 FA TRANSPARENT FUNCTION 31 1 ...
Page 676: ......
Page 742: ...31 66 31 FA TRANSPARENT FUNCTION 31 7 Precautions ...
Page 744: ......
Page 766: ...32 22 32 CONNECTION TO IAI ROBOT CONTROLLER 32 7 Precautions ...
Page 802: ...34 10 34 CONNECTION TO OMRON TEMPERATURE CONTROLLER 34 7 Precautions ...
Page 834: ...36 18 36 CONNECTION TO KOYO EI PLC 36 6 Device Range that Can Be Set ...
Page 858: ...38 12 38 CONNECTION TO SHARP PLC 38 6 Device Range that Can Be Set ...
Page 868: ...39 10 39 CONNECTION TO SHINKO TECHNOS INDICATING CONTROLLER 39 7 Precautions ...
Page 902: ...42 6 42 CONNECTION TO TOSHIBA MACHINE PLC 42 6 Device Range that Can Be Set ...
Page 908: ...43 6 43 CONNECTION TO PANASONIC SERVO AMPLIFIER 43 7 Precautions ...
Page 970: ...48 12 48 CONNECTION TO FUJI TEMPERATURE CONTROLLER 48 7 Precautions ...
Page 1052: ...52 26 52 CONNECTION TO AZBIL CONTROL EQUIPMENT 52 7 Precautions ...
Page 1102: ...55 14 55 CONNECTION TO GE PLC 55 7 Precautions ...
Page 1114: ...57 4 57 CONNECTION TO SICK SAFETY CONTROLLER 57 5 Device Range that Can Be Set ...
Page 1128: ...59 2 59 CONNECTION TO HIRATA CORPORATION HNC CONTROLLER ...
Page 1130: ...60 2 60 CONNECTION TO MURATEC CONTROLLER ...
Page 1132: ......
Page 1270: ...62 68 62 MICROCOMPUTER CONNECTION ETHERNET 62 8 Precautions ...
Page 1271: ...MODBUS CONNECTIONS 63 MODBUS R RTU CONNECTION 63 1 64 MODBUS R TCP CONNECTION 64 1 ...
Page 1272: ......
Page 1292: ...64 12 64 MODBUS R TCP CONNECTION 64 7 Precautions ...
Page 1293: ...CONNECTIONS TO PERIPHERAL EQUIPMENT 65 VNC R SERVER CONNECTION 65 1 ...
Page 1294: ......
Page 1298: ...65 4 65 VNC R SERVER CONNECTION 65 4 Setting in Personal Computer ...
Page 1302: ...REVISIONS 4 ...
Page 1305: ......
Page 1306: ......