MI 3321 MultiservicerXA
Technical specifications
21
3.7 Differential Leakage current
Differential leakage current
Range
Resolution
Accuracy
0.00 mA
… 9.99 mA
0.01 mA
(5 % of r 5 digits)
Pass levels [mA]: ...................... 0.25, 0.50, 0.75, 1.00, 1.50, 2.50, 3.00 mA, 3.50, 4.00,
4.50, 5.00, 5.50, 6.00, 7.00, 8.00, 9.00, none
Test duration [s] ........................ 5, 10, 30, 60, 120, none
Frequency response: ................ complies to EN 61010-1, Figure A1
Test terminals:
Differential leakage
mains test socket
3.8 Power / Functional test
Apparent power
Range
Resolution
Accuracy
0.00 kVA
… 4.00 kVA
0.01 kVA
(5 % of r 3 digits)
Test duration [s]: ....................... 5, 10, 30, 60, 120, none
Test terminals:
Power
mains test socket
3.9 Touch leakage current
Touch leakage current
Range
Resolution
Accuracy
0.00 mA
… 2.50 mA
0.01 mA
(10 % of r 5 digits)
Pass levels [mA]: ...................... 0.25, 0.50, 0.75, 1.00, 1.50, 2.00, none
Test duration [s]: ....................... 5, 10, 30, 60, 120, none
Output: ...................................... test socket, test probe connector
Impedance,
Frequency response: ................ complies to EN 61010-1, Figure A1
Test terminals:
Touch leakage
mains test socket or external source/ S
3.10 Polarity test
Test voltage .............................. <50 V AC
Detects ..................................... Pass, L-open, N-open, PE-open, L-N crossed, L-PE
crossed, N-PE crossed, L-N shorted, L-PE shorted, N-
PE shorted, multiple faults
Test terminals:
Differential leakage
Mains test socket ↔ IEC