MI 3321 MultiservicerXA
Switchgear testing operating mode
158
Test circuit for Discharging Time test
Discharging time test
Trip out current measurement procedure
Select the
Discharging Time
single test.
Set test
parameters
.
Connect
three wire test cable to the TP1 test port on the instrument.
Connect
L and N wires of the three wire test cable to terminals to be tested.
Press the
START
key to start the measurement.
Wait
until “
Ready
” is displayed
Disconnect
the switchboard. “Wait” is displayed until the residual voltage drops
below 120V. If the voltage at disconnection moment is too low to get an accurate
result “Repeat” is displayed. The measurement must be repeated.
Press
SAVE
(F4) key for storing the result (optional).