MI 3321 MultiservicerXA
Machine testing operating mode
116
Visual test procedure
Select the
VISUAL TEST
function.
Perform visual
inspection
of the machine.
Commit
PASS or FAIL
ticker manually (with
PASS
(F1),
FAIL
(F5) keys.
Save result (optionally) with
SAVE
(F4) key.
Examples of visual test measurement results
9.2.2
Continuity
This test determines that the PE and equipotential connections inside the machine have
proper resistance that corresponds to their length and cross-section.
Continuity menus
Test parameters for Continuity measurement
OUTPUT
Test
current
[200 mA, 10 A]
LIMIT
Maximum resistance
[0.01
… 0.09
, 0.10
… 0.90
,
1.00
… 9.00
]
TIME
Measuring time
[5 s, 10 s, 30 s, 60 s, 120 s, 180 s]
MODE
Operation mode
[single, auto]