MI 3321 MultiservicerXA
Switchgear testing operating mode
148
Measurement of continuity of protective conductors of switchboards
10.2.2.1 Single continuity test
In the single continuity test the continuity of individual connections can be determined.
Continuity measurement procedure
Select the
CONTINUITY
function.
Set test
parameters
Make sure that the test leads are calibrated. Calibrate them if necessary (See
chapter
10.2.2.3 Compensation of test leads resistance
for more information).
Connect
test leads to S/C1 and C2 terminals on the instrument.
Connect
test leads to both ends of protective conductor under test.
Press the
START
key for measurement.
Press
SAVE
(F4) key for storing the result (optional).