MI 3321 MultiservicerXA
All tests operating mode
166
values set on base of selected protective circuit breakers. The measurement complies
with requirements of the standard EN 61557-3.
Warning!
MI 3321 checks voltages on TP1 before running test and disables test in
case hazardous live voltage is detected on TP1 PE. In this case,
immediately remove supply from test circuit, find and eliminate problem
before any other activity!
Line impedance menu
Test parameters for line impedance measurement
Test
Type of test [Z LINE, Z m
L-N**, Z m
L-L**]
Fuse type
Selection of
fuse
type
[*F, NV, Gg, B, C, K, D]
Fuse I
Rated current
of selected fuse
Fuse T.
Maximum
breaking time
of selected fuse
Isc_lim
Minimum short circuit
current
for selected fuse combination.
»*F« means no fuse selected.
** See
chapter 11.1.14.1
for low line impedance measurement procedure.