MI 3321 MultiservicerXA
Switchgear testing operating mode
147
Commit
PASS
or
FAIL
ticker manually (with PASS(F1), FAIL(F5) keys.
Save result (optionally) with
SAVE
key
Examples of visual test measurement results
10.2.2 Continuity
This test determines that the PE and equipotential connections inside the switchboard
have a proper resistance that corresponds to their length and cross-section.
Continuity menus
Test parameters for Continuity measurement
OUTPUT
Test
current
[200 mA, 10 A]
LIMIT
Maximum resistance
[0.01
… 0.09
, 0.10
… 0.90
,
1.00
… 9.00
]
TIME
Measuring time
[5 s, 10 s, 30 s, 60 s, 120 s, 180 s]
MODE
Operation mode
[single, auto]
Test circuit for Continuity measurement