Switchgear testing operating mode
146
<
RCD test
>, Tests of residual current devices.
<
PRCD test
> Tests of portable residual current devices,
<
Functional test
>, Functional inspection.
<
Power
>, Power consumption test.
ENTER
Enters selected test.
ESC
Returns to Main menu.
Note:
Unlike in PAT testing mode all single test results and parameters can be stored for
documentation purposes (see chapter 12.1 for more information).
10.2 Measurements and inspections
10.2.1 Visual test
Visual check is the most important and effective part of a switchgear test.
Electrical testing often does not disclose failures that become apparent on visual
inspection. A visual check must be carried out before each electrical safety test.
Following items should be checked:
- Wiring connection points,
- Protection covers, housings,
- Inscriptions and markings especially that related to safety,
- Cables (layout, radiuses, isolation),
- Switches, regulators, lamps, keys,
- Electrical and mechanical protection devices (barriers, switches, fuses, alarms),
- Technical documentation.
During visual inspection the measuring points for the electrical testing have to be
determined too.
Check that there are no signs of:
- Damage,
- Pollution, moisture, dirt that can jeopardize safety,
- Corrosion,
- Overheating.
Visual test menu
Visual test procedure
Select the
VISUAL TEST
function.
Perform
visual inspection
of the switchgear.