MI 3321 MultiservicerXA
Technical specifications
28
3.16 Voltage, frequency, and phase rotation
3.16.1 Phase rotation
Result displayed
1.2.3 or 3.2.1
Nominal system voltage range: 100 V
AC
… 550 V
AC
Nominal frequency range: ......... 14 Hz
… 500 Hz
Test terminals:
Phase rotation
TP1 test socket
3.16.2 Voltage, Frequency
Range
Resolution
Accuracy
0
… 550 V
1 V
(2 % of r 2 digits)
Range (Hz)
Resolution (Hz)
Accuracy
0.0, 14.0
… 499.9
0.1
(0.2 % of r 1 digit)
Result type: ............................... True r.m.s. (trms)
Nominal frequency range: ......... 0 Hz, 14 Hz
… 500 Hz
Nominal voltage range: ............. 10 V
… 550 V
Test terminals:
VOLTAGE
TP1 test socket
3.17 General data
Power supply
Rated supply voltage: ............... 115 V / 230 V AC
Supply voltage tolerance: .........
10 %
Frequency of supply voltage: .... 50 Hz, 60 Hz
Max. power consumption: ......... 300 VA (without DUT)
Rated DUT: ............................... 16 A resistive, 1.5 kW motor
Overvoltage category
Instrument: ................................ CAT II / 300 V
Test socket: .............................. CAT II / 300 V
TP1 test socket: ........................ CAT III / 300 V
Plug test cable: ......................... 300 V CAT II
Universal test cable: ................. 300 V CAT III
Altitude: .....................................
≤
2000 m
Protection classification
HV output: ................................. Class I
TP1 test socket: ........................ Class II, double insulation