Using a Single Phase Power Source
458
Single-Phase Rating (200V/60Hz)*
[kW] [HP]
Single-Phase Current Rating
Wire
Selection
FUSE
DC Link
Choke
MCCB
Electronic
Contactor
Output Amp Input Amp
AWG
HD [A] ND [A] HD [A] ND [A] R,S,T U,V,W [A] [V]
[mH] [A] LS ELECTRIC(UL Type)
0.75kW 1
2.6
4.1
4.3
6.8
14 14
10
500V
Built-in
UTE100/15A
MC-9b
1.5kW 2
4.0
6.0
6.9
10.6 14 14
15
UTE100/15A
MC-12b
2.2kW 3
6.2
8.2
11.2 14.9 14 14
20
UTE100/30A
MC-18b
3.7kW 5
8.1
12
14.9 21.3 12 12
32
UTE100/30A
MC-32a
5.5kW 7.5 12
16
22.1 28.6 10 10
50
UTS150/50A
MC-40a
7.5kW 10 16
23
28.6 41.2 8
8
63
UTS150/60A
MC-50a
11kW 15 24
31
44.3 54.7 6
6
80
UTS150/100A MC-65a
15kW 20 31
38
55.9 69.7 4
4
100
UTS150/125A MC-100a
18.5kW 25 38
45
70.8 82.9 2
2
125
UTS150/150A MC-130a
22kW 30 45
64
85.3 116.1 1
1
160
UTS250/175A MC-150a
30kW 40 60
75
121.0 152.0 1/0 1/0
200
0.24 200 UTS250/225A MC-150a
37kW 50 75
93
154.0 190.0 2/0 2/0
250
0.2 240 UTS400/300A MC-225a
45kW 60 93
114
191.0 231.0 2/0 2/0
350
0.17 280 UTS400/350A MC-330a
55kW 75 114 149
233.0 302.0 3/0 3/0
400
0.12 360 UTS600/500A MC-400a
75kW 100 149 178
305.0 362.0 4/0 4/0
450
0.1 500 UTS600/600A MC-630a
*The drive ratings in Table 1 are valid for 60 Hz input only.
Table 1. Single-Phase Rating(240 V/60 Hz)
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...