Learning Advanced Features
Adv
anc
ed
Feat
ur
es
255
[Example of auto restart with a setting of 2]
If the auto restart number is set, be careful when the inverter resets from a fault trip. The motor may
automatically start to rotate.
8.21
Operational Noise Settings (Carrier Frequency
Settings)
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
CON
04
Carrier
Frequency
Carrier Freq 5.0
0.7
–
15.0
kHz
05
Switching Mode PWM* Mode 0
Normal PWM Normal PWM / Low
Leakage PWM
-
* PWM: Pulse width modulation
Operational Noise Setting Details
Code
Description
CON-04
Carrier Freq
Adjusts motor operational noise by changing carrier frequency settings. Power
transistors (IGBT) in the inverter generate and supply high frequency switching
voltage to the motor. The carrier frequency refers to the switching speed in
this process. If the carrier frequency is set high, it reduces operational noise
from the motor. If the carrier frequency is set low, it increases operational