263
8.26
Input Power Voltage Settings
Set the inverter input power voltage. The low voltage fault trip level changes automatically
according to the set voltage standard.
Group Code Name
LCD Display Parameter Setting
Setting Range
Unit
BAS
19
Input power voltage
AC Input
Volt
200 Type 220
170
–
230
V
400 Type 380
380
–
480
8.27
Read, Write, and Save Parameters
Use read, write, and save parameter functions to copy parameters from the inverter to the
keypad or from the keypad to the inverter.
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
CNF
46
Parameter read
Parameter Read
1 Yes
-
-
47
Parameter write Parameter Write
1 Yes
-
-
48
Parameter save
Parameter Save
1 Yes
-
-
Read, Write, and Save Parameter Setting Details
Code
Description
CNF-46 Parameter Read
Copies saved parameters from the inverter to the keypad. Saved
parameters on the keypad will be deleted and replaced with the copied
parameters.
CNF-47 Parameter Write
Copies saved parameters from the keypad to the inverter. Saved
parameters on the inverter will be deleted and replaced with the copied
parameters. If an error occurs during parameter writing, the previously
saved data will be used. If there is no saved data on the keypad, “EEP
Rom Empty
” will be displayed.
CNF-48 Parameter Save
As parameters set during communication transmission are saved in
RAM, the setting values will be lost if the power turns off and on. When
setting parameters during communication transmission, select “1 (Yes)”
at CNF-48 to save the set parameters.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...