Using Protection Features
346
10.2.14
Trip Status Reset
Group
Code
LCD Display
Parameter Setting
Unit
IN
65-72
Px Define
3
RST
-
Trip Status Reset Setting Details
Code
Description
IN-65
–
72 Px Define
Press the [Stop/Reset] key on the keypad or use the multi-function input
terminal to restart the inverter. Set the multi-
function input terminal to “3
(RST)
”
and turn on the terminal to reset the trip status.
10.2.15
Operation Mode On Optional Expansion Module Fault Trip
Optional extension module
trips may occur when an optional extension module is used with
the inverter. Set the operation mode for the inverter when a communication error occurs
between the optional extension module and the inverter body, or when the optional extension
module is detached during operation.
Group
Code
LCD Display
Parameter Setting
Unit
PRT
80
Opt Trip Mode
0
None
1:Free-Run
1
Free-Run
2
Dec
Optional Expansion Module Fault Trip Setting Details
Code
Description
PRT-80 Opt Trip
Mode
Setting
Function
0 None
No operation
1 Free-Run The inverter output is blocked and fault trip information is
shown on the keypad.
2 Dec
The motor decelerates to the value set at PRT-07 (Trip Dec
Time).