407
Table of Functions
Func
tio
n
Table
13.3
Parameter Mode
–
Expansion Function Group
(PAR
ADV)
Expansion Function Group (PAR
ADV)
No.
Communi-
cation
Address
LCD Display Name
Setting Range
Initial
Value
Shift in
Opera-
tion
Page
Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
00 -
Jump Code
Jump code
0
–
99
24
O
-
O O O O O
01 0h1301
Acc Pattern
Acceleration pattern
0 Linear
0:Linear X
171 O O O X X
02 0h1302
Dec Pattern
Deceleration pattern
1 S-curve
X
171 O O O X X
03 0h1303
Acc S Start
S-curve acceleration start
point gradient
1
–
100 (%)
40
X
171 O O O X X
04 0h1304
Acc S End
S-curve acceleration end
point gradient
1
–
100 (%)
40
X
171 O O O X X
05 0h1305
Dec S Start
S-curve deceleration start
point gradient
1
–
10 0 (%)
40
X
171 O O O X X
06 0h1306
Dec S End
S-curve deceleration end
point gradient
1
–
100 (%)
40
X
171 O O O X X
07 0h1307
Start Mode
Start mode
0 Acc
0:Acc
X
183 O O O X X
1 Dc-Start
08 0h1308
Stop Mode
Stop mode
0 Dec
0:Dec
X
185 O O O X X
1 Dc-Brake
2 Free-Run
3 Flux Braking
4 Power Braking
09 0h1309
Run Prevent
Selection of prohibited
rotation direction
0 None
0:None X
162 O O O X X
1 Forward Prev
2 Reverse Prev
10 0h130A
Power-on Run Start with power on
0 No
0:No
O
163 O O O X X
1 Yes
12
Note8)
0h130C
Dc-Start Time Starting DC braking time 0
–
60 (sec)
0.00
X
280 O O O X X
13 0h130D
Dc Inj Level
DC supply
0
–
200 (%)
50
X
280 O O O X X
14
Note9)
0h130E
Dc-Block Time Output blocking time
before DC braking
0
–
60 (sec)
0.10
X
185 O O O X X
15 0h130F
Dc-Brake Time DC braking time
0
–
60 (sec)
1.00
X
185 O O O X X
16 0h1310
Dc-Brake Level DC braking rate
0
–
200 (%)
50
X
185 O O O X X
17 0h1311
Dc-Brake Freq DC braking frequency
Starting frequency
–
60 (Hz) 5.00
X
185 O O O X X
20 0h1314
Acc Dwell Freq Acceleration dwell
frequency
Starting frequency
–
maximum frequency (Hz) 5.00
X
280 O O O X X
21 0h1315
Acc Dwell Time Acceleration dwell
operation time
0
–
60.0 (sec)
0.00
X
280 O O O X X
22 0h1316
Dec Dwell Freq Deceleration dwell
frequency
Starting frequency
–
maximum frequency (Hz) 5.00
X
280 O O O X X
23 0h1317
Dec Dwell Time Deceleration dwell
operation time
0
–
60.0 (sec)
0.00
X
280 O O O X X
* The grey cells indicate a hidden code which is only visible when setting a code.
Note 8)
ADV-12 is displayed only when ADV-07
“Stop Mode” is set as “D
C-
Start”.
Note 9)
ADV-14
–
17 is displayed only when ADV-
08 “Stop Mode” is set as “DC
-
Brake”.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...