Communication Function
361
11.12
Parameter Group for Transmission of Macro
Group and User Group at U&M Mode
By defining the user and macro parameter groups, communication can be carried out using
the user defined user group (USR) and macro group (MAC) addresses that are registered in
U&M mode.
Addresses
Description
U&M>USR-1
–
64
User Grp. Para h
Writes and reads the USR parameters set by the keypad via the addresses
0h0200
–
0h023F.
Address Parameter
Allotment for Bits
0h0200 User Grp. Code 1
Parameter value registered at U&M>USR->1
0h0201 User Grp. Code 2
Parameter value registered at U&M>USR->2
...
.
.
...
.
.
...
.
.
0h023E User Grp. Code 63 Parameter value registered at U&M>USR->63
0h023F User Grp. Code 64 Parameter value registered at U&M>USR->64
U&M>MAC-1
–
64
Macro Grp. Para
h
Writes and reads the Macro parameters set by the keypad via the addresses
0h2400
–
0h2A3.
Address Parameter
Allotment for Bits
0h0240 Macro Grp. Code 1
Parameter value registered at U&M>MAC-1
0h0241 Macro Grp. Code 2
Parameter value registered at U&M>MAC-2
...
.
.
...
.
.
...
.
.
0h02A2 Macro Grp. Code 63 Parameter value registered at U&M>MAC-63
0h02A3 Macro Grp. Code 64 Parameter value registered at U&M>MAC-64
11.13
Communication Protocol
11.13.1
LS INV 485 Protocol
The slave device (inverter) responds to read and write requests from the master device (PLC or
PC).
Request
ENQ
Station ID
CMD
Data
SUM
EOT
1 byte
2 bytes
1 byte
n bytes
2 bytes
1 byte
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...