Connecting the Cables
73
Note
•
The TR (termination resistor) switch is used to terminate the RS485 network connection (120
Ω
).
•
Use a potentiometer rated for 0.5 W, 1 k
Ω
.
If the analog voltage (V) or current (I) input is used to set the frequency reference, the analog
input is reflected when the input is actually received. For instance, the voltage input 0 V at V1
does not indicate that no input is received at V1, but it means that 0 V input is actually received
at V1.
Note
When you use the analog voltage input, the bipolar input range (-10
–
+10V), in comparison to the
unipolar input range (0
–
10V), allows for more accurate input control with smaller increments.
If the analog input is interrupted when setting a frequency reference using the analog voltage (V)
input and no voltage input is received at the terminal, an offset voltage may be applied to keep the
frequency reference at approximately 4
–
5 Hz.
4.10
Terminal Inputs for Inverter Operation
Input Type
Symbol Name
Description
In
pu
t s
ig
na
l
Terminal
input
P1
–
P8
Multi-function
input1
–
8
Configurable for multi-function input terminals.
Refer to
for the
multi-function terminal configurations.
CM
Common sequence
Common terminal for terminal inputs (5G common
terminal is used for analog frequency inputs only).
Analog
input
VR(+)
Potentiometer
frequency reference
(+)
Used to setup or modify a frequency reference via
the analog voltage or current input.
Maximum output is +12 V, 100 mA.
VR(-)
Potentiometer
frequency reference
(-)
Used to setup or modify a frequency reference via
the analog voltage or current input.
Maximum output is -12 V, 100 mA.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...