Communication Function
386
Address
Parameter
Scale unit
Changeable
During
Operation
Function
Page
setup mode)
0h03EA
note1)
Initializing
power
consumption
-
-
O
0: No
1: Yes
0h03EB
note1)
Initialize inverter
operation
accumulative
time
-
-
O
0: No
1: Yes
0h03EC
note1)
Initialize cooling
fan
accumulated
operation time
-
-
O
0: No
1: Yes
Note 1
- Set parameters very carefully. After setting a parameter to
“
0
“
via communication, set it to another
value. If a parameter has been set to a value other than 0 and a non-zero value is entered again, an
error message is returned. The previously set value can be identified by reading the parameter
when operating the inverter via communication.
Note that the execution time may take longer because the data is saved in the inverter, possibly
interrupting communication.
Note 2
- The addresses 0h03E7 and 0h03E8 are parameters for entering the password. When the
password is entered, the condition will change from
“
Lock
”
to
“
Unlock
”
, and vice versa.
When the same parameter value is entered repeatedly, the parameter setting is executed just once.
To enter the same value, change it to another value first and then re-enter the previous value. For
example, if you want to enter 244 twice, enter it in the following order: 244 -> 0 -> 244.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...