Basic Functions
168
7.10.3
Multi-Step Acc/Dec Time Configuration
The acc/dec times can be configured via a multi-function terminal by setting the ACC
(acceleration time) and DEC (deceleration time) codes in the DRV group.
Group Code Name
LCD Display Parameter Setting
Setting Range Unit
DRV
03
Acceleration time
Acc Time
75 kW and less 20.0
0.0
–
600.0
sec
90 kW and up 60.0
04
Deceleration time
Dec Time
75 kW and less 30.0
0.0
–
600.0
sec
90 kW and up 90.0
BAS
70,
72,
74
Multi-step
acceleration time1
–
3
Acc Time
–
x x.xx
0.0
–
600.0
sec
71,
73,
75
Multi-step
deceleration time1
–
3
Dec Time
–
x x.xx
0.0
–
600.0
sec
IN
65
–
75
Px terminal
configuration
Px Define
(Px: P1
–
P8
[optional:
P9
–
P11])
11
XCEL-L
-
-
12
XCEL-M
49
XCEL-H
89
Multi-step command
delay time
In Check
Time
1
1
–
5000
ms
Acc/Dec Time Setup via Multi-function Terminals
–
Setting Details
Code
Description
BAS-70, 72, 74
Acc Time 1
–
3
Set multi-step acceleration time 1
–
3.
BAS-71, 73, 75
Dec Time 1
–
3
Set multi-step deceleration time 1
–
3.
IN-65
–
75
Px Define (P1
–
P8
[optional P9
–
P11])
Choose and configure the terminals to use for multi-step acc/dec time
inputs.
Configuration
Description
11
XCEL-L
Acc/Dec command-L
12
XCEL-M
Acc/Dec command-M
49
XCEL-H
Acc/Dec command-H
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...