Using Monitor Functions
Code
Description
AO2
Bias
0.0%
20.0%
(factory
Default)
OUT-10 AO2 Filter Sets the filter time constant of the analog output.
OUT-11 AO2
Const %
Sets the analog output items to Constant (AO2 Mode: 15), and then the analog
current is output at the value of the parameters set.
OUT-12 AO2
Monitor
Monitors the analog output value, which is represented as a percentage based
on the 20 mA maximum output voltage.
Note
When 4
–
20 mA is used as the output, tune OUT-08 AO2 Gain and OUT-09 AO2 Bias as follows.
1
Set OUT-07 AO2 Mode to Constant and OUT11 AO2 Const % to 0.0%.
2
After setting OUT-09 AO2 Bias to 20.0%, ensure that that the current is 4 mA. If the current is
lower than 4 mA, gradually increase OUT-09 AO2 Bias until it measures 4 mA. If the current is
higher than 4 mA, gradually decrease OUT-09 AO2 Bias until it measures 4 mA.
3
Set OUT11 AO2 Const % to 100.0%. After setting OUT-08 AO2 Gain to 80.0%, ensure that the
current is 20 mA. If the current is lower than 20 mA, gradually increase OUT-08 AO2 Gain until it
measures 20 mA. If the current is higher than 20 mA, gradually decrease OUT-08 AO2 Gain until
it measures 20 mA.
4
When 0-20 mA is used as the output, set OUT-08 A02 Gain to 100% and OUT-09 A02 Bias to
0.0%.
5
The functions for each code are the same as the item of 0
–
10 V output. And, the output range is
0
–
20 mA.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...