Basic Functions
161
B
as
ic
Func
tio
ns
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
CNF
42
[MULTI] key
functions
Multi-Key Sel
2 Local/Remote -
-
DRV
06
Command source
Cmd Source
1 Fx/Rx-1
0
–
5
-
Local/Remote Mode Switching Setting Details
Code
Description
CNF-42
[MULTI] key
functions
Set CNF-42 to
“
2(Local/Remote)
”
to perform local/remote mode switching
using the [MULTI] key.
Once the parameter is set,
“R”
(remote) is displayed on the keypad, and the
inverter will automatically begin operating in remote mode. Changing from
local to remote operation will not alter any previously configured parameter
values and the operation of the inverter will not change.
Press the [MULTI] key to switch the operation mode to
“
local.
”
“
L
”
(local) is displayed on the keypad, and the command source and frequency
source indication on the keypad (in MON mode) changes to
“
K/K.
”
The inverter stops operating if it was previously running in remote mode, and
you can operate the inverter using the keypad.
Press the [MULTI] key again to switch the operation mode back to
“
remote.
”
“R”
(remote) is displayed again on the keypad, and the command source and
frequency source indication on the keypad (in MON mode) changes according
to the previous parameter settings.
The inverter is now ready to operate in remote mode, and the inverter
operation may vary depending on the type of input source.
Note
Local/Remote Operation
•
Full control of the inverter is available with the keypad during local operation.
•
During local operation, jog commands will only work if one of the multi-function terminals (Px:
P1
–
P11, codes IN-65
–
75) is set to
“
1
3 (RUN Enable)”
and the relevant terminal is turned on.
•
During remote operation, the inverter will operate according to the previously set frequency
reference source and the command received from the input device.
•
If ADV-10 (power-on run) is set to
“
0
(No)”
, the inverter will not operate on power-on even when
the following terminals are turned on:
- Fwd/Rev run (Fx/Rx) terminal
- Fwd/Rev jog terminal (Fwd jog/Rev Jog)
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...