283
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
APP
01
Application mode
App Mode
3
MMC
-
-
APO
20
Aux motor rotation
number
Aux Motor Run -
0
0
–
4
-
21
Starting aux motor
selection
Starting Aux
-
1
1
–
4
-
22
Auto operation time Auto Op Time
-
0:00
xx:xx
Min
23
1st aux motor
starting frequency
Start Freq 1
-
49.99
0
–
60
Hz
24
2nd aux motor
starting frequency
Start Freq 2
-
49.99
0
–
60
Hz
25
3rd aux motor
starting frequency
Start Freq 3
-
49.99
0
–
60
Hz
26
4th aux motor
starting frequency
Start Freq 4
-
49.99
0
–
60
Hz
27
1st aux motor stop
frequency
Stop Freq 1
-
15.00
0
–
60
Hz
28
2nd aux motor stop
frequency
Stop Freq 2
-
15.00
0
–
60
Hz
29
3rd aux motor stop
frequency
Stop Freq 3
-
15.00
0
–
60
Hz
30
3th aux motor stop
frequency
Stop Freq 4
-
15.00
0
–
60
Hz
31
Aux motor starting
delay time
Aux Start DT
-
60.0
0
–
3600.0
Sec
32
Aux motor stop
delay time
Aux Stop DT
-
60.0
0
–
3600.0
Sec
APO
33
Aux motor number
selection
Num of Aux
-
4
0
–
4
-
34
Bypass selection
Regul Bypass
0
No
0
–
1
-
35
Auto change mode
selection
Auto Ch Mode
0
Aux
None/Aux/Mai
n
-
36
Auto change time
Auto Ch Time
-
72:00
0
–
99:00
Min
38
Interlock selection
Interlock
0
No
0
–
1
-
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...