Basic Functions
186
Code
Description
to the motor. Prevent overcurrent fault trips by adjusting the output block time
before DC braking.
ADV-15 DC-
Brake Time
Sets the time duration for the DC voltage supply to the motor.
ADV-16 DC-
Brake Level
Sets the amount of DC braking to apply. The parameter setting is based on the
rated current of the motor.
ADV-17 DC-
Brake Freq
Sets the frequency to start DC braking. When the frequency is reached, the
inverter starts deceleration. If the dwell frequency is set lower than the DC
braking frequency, the dwell operation will not work and DC braking will start
instead.
•
The motor can overheat or be damaged if an excessive amount of DC braking is applied to the
motor or if the DC braking time is set to a high value.
•
DC braking is configured based on the motor’s rated current. To prevent overheating or
damaging motors, do not set the current value higher than the in
verter’s rated current.
7.17.3
Free Run Stop
When the operation command is off, the inverter output turns off, and the load stops due to
residual inertia.