Using Monitor Functions
320
9.5
Fault trip output using multi-function output
terminals and relays
The inverter can output a fault trip state using the multi-function output terminal (Q1) and relay
(Relay1).
Group
Code
LCD Display
Parameter Setting
Unit
OUT
30
Trip Out Mode
-
010
31
Relay 1
29
Trip
-
32
Relay 2
14
Run
-
33
Q1 Define
1
FDT-1
-
53
Trip Out On Dly
-
0.00
Sec
54
Trip Out Off Dly
-
0.00
Sec
* The inverter can output a fault trip status using expansion digital output terminals (OUT 34
–
36) if
the optional I/O expansion module is installed.
Code
Description
OUT-30 Trip
Out Mode
Set OUT-30 (Trip Out Mode) to enable or disable the fault relay.
Bit on
Bit off
Depending on the fault trip type, the terminal and relay operation can be
configured as shown in the table below.
Setting option
Function
Bit3
Bit2
Bit1
The top-right corner of the display is
‘Bit 1’
.
Operates when a low voltage fault trip occurs.
Operates when a fault trip other than low voltage
occurs.
Operates when auto restart fails (PRT-08
–
09).
OUT-31
–
33
Select the terminal and relay to use for failure output and set OUT-31
–
33 to
“28
(Trip
mode)
”
. When a fault trip occurs in the inverter, the relevant terminal and relay will
operate.
OUT-53 Trip
Out On Dly,
If a fault trip occurs, trip relay or multi-function output operates after the time delay
set in OUT-53. The terminal turns off with the input initialized after the time delay
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...