Using a Single Phase Power Source
460
16.5
Other Considerations
The following lists other precautions that need to be considered when using a three-phase VFD
using single-phase power source.
•
Depending on the increased DC ripple, sensorless mode may result in poor performance
when operating a three-phase inverter using single-phase power supply.
•
If a phase open trip occurs, cancel the input phase open protection bit setting (PRT-05:
Phase Loss Chk).
•
Do not allow the current to exceed the single-phase rating. Motor capacity, motor overload
trip, and E-thermal functions must be set to protect motor.
•
A reactor is always required. Use a model type that comes with built-in DC reactor. The iS7
200 V 30
–
75kW and 400 V 280
–
375 kW products do not have built-in DC reactors. Install an
external AC reactor separately for these model types (Do not install DC reactors externally).